Transmission line model errors under variations in length and loading

Authors

DOI:

https://doi.org/10.46842/ipn.cien.v30n2a09

Keywords:

transmission lines, ABCD parameters, nominal π model, active power losses, error analysis

Abstract

The short-line, nominal π, and distributed-parameter models are compared to determine how their steadystate discrepancies vary with line length, loading level, and power factor. A balanced three-phase 400 kV and 50 Hz configuration is analyzed under 168 operating conditions obtained by combining 14 lengths from 20 to 400 km, four active-power levels, and three power factors. The formulations are implemented in MATLAB using ABCD parameters, common inputs, and the distributed-parameter model as the mathematical reference. For the short-line model, the median sending-end voltage and current magnitude errors are 1.5206% and 6.3772%, with maxima of 9.7545% and 55.0435%, respectively. For the nominal π model, the corresponding medians are 0.0134% and 0.0203%, and the maxima are 0.7304% and 1.6167%. However, the maximum relative active-power-loss error reaches 18.8181% for the nominal π model. The results show that close agreement in terminal magnitudes does not necessarily imply an equally small relative discrepancy in active-power losses and that model assessment should consider both the indicator and the operating condition. The conclusions are limited to the investigated configuration and parametric domain, without establishing universal length thresholds or attributing experimental accuracy to the distributed-parameter model used as the mathematical reference.

References

[1] J. J. Grainger, W. D. Stevenson, Jr., Power System Analysis, New York, NY, USA: McGraw-Hill, 1994.

[2] J. D. Glover, T. J. Overbye, M. S. Sarma, Power System Analysis and Design, 6th ed., USA: Cengage Learning, 2017.

[3] H. Saadat, Power System Analysis, 3rd ed., USA: PSA Publishing, 2010.

[4] M. S. Mamis, M. Koksal, “Remark on the lumped parameter modeling of transmission lines,” Electric Machines and Power Systems, vol. 28, no. 6, pp. 565–575, 2000, doi: https://doi.org/10.1080/073135600268180

[5] L. Yuan, T. Nguyen, “Alternative way to derive equivalent PI circuit model of transmission lines,” in Proc. 39th Southeastern Symposium on System Theory (SSST), Macon, GA, USA, 2007, pp. 186–188, doi: https://doi.org/10.1109/SSST.2007.352345

[6] N. Kang, Y. Liao, “Equivalent PI circuit for zero-sequence double circuit transmission lines,” in 2012 IEEE Power and Energy Society General Meeting, San Diego, CA, USA, 2012, Art. no. 6344945, doi: https://doi.org/10.1109/PESGM.2012.6344945

[7] N. V. Souza, Jr., C. G. Carvalho, S. Kurokawa, J. Pissolato, “A distributed-parameters transmission line model developed directly in the phase domain,” Electric Power Components and Systems, vol. 41, no. 11, pp. 1100–1113, 2013, doi: https://doi.org/10.1080/15325008.2013.809823

[8] B. Poudel, V. Cecchi, “Frequency-dependent models of overhead power lines for steady-state harmonic analysis: Model derivation, evaluation and practical applications,” Electric Power Systems Research, vol. 151, pp. 266–272, 2017, doi: https://doi.org/10.1016/j.epsr.2017.05.038

[9] J. P. R. Balestero, J. S. L. Colqui, S. Kurokawa, “Using the exact equivalent π-circuit model for representing three-phase transmission lines directly in the time domain,” Energies, vol. 16, no. 20, Art. no. 7192, 2023, doi: https://doi.org/10.3390/en16207192

[10] L. Quayyoom, O. Rahman, F. I. Bakhsh, A. Ahmad, “Optimal power flow and computer-based analysis of a simultaneous AC–DC power transmission system,” IET Generation, Transmission & Distribution, vol. 18, no. 23, pp. 3777–3787, 2024, doi: https://doi.org/10.1049/gtd2.13101

[11] O. O.-S. Ojah, Y. Naenwi, P. O. Odu, “Model transmission line parameters evaluation using Matlab: A case study of short-line and nominal-Pi methods,” European Journ. of Adv. in Engineering and Technology, vol. 12, no. 2, pp. 42–46, 2025.

[12] İ. Arı, R. Menak, “Lumped-parameter transmission line modeling using MATLAB/Simulink,” Balkan Journal of Electrical and Computer Engineering, vol. 13, no. 3, pp. 286–294, 2025, doi: https://doi.org/10.17694/bajece.1761735

[13] M. R. Araújo, E. A. Batista, “A practical first-zone distance protection formulation based on the nominal π transmission line model,” Electric Power Systems Research, vol. 246, Art. no. 111665, 2025, doi: https://doi.org/10.1016/j.epsr.2025.111665

[14] The MathWorks, Inc., Simscape Electrical User's Guide (Specialized Power Systems), ver. 7.3, Release R2020a. Natick, MA, USA: The MathWorks, Inc., 2020.

Downloads

Published

28-10-2026

How to Cite

Transmission line model errors under variations in length and loading. (2026). Científica, 30(2), 1-15. https://doi.org/10.46842/ipn.cien.v30n2a09